Concerns of Power Factor Capacitor Applications

The increasing cost of energy and penalties set by many electric utility companies are resulting in a widespread application of power factor correction capacitors. However, their application can lead to harmonic and transient problems which need to be addressed. Benefits and guidelines for power factor correction are covered in the companion paper on this system. This paper will attempt to clarify the concerns resulting from their application.

HARMONIC CONCERNS OF SHUNT CAPACITORS

Power factor capacitors can drastically change the frequency response of an industrial power system. Figure 1 illustrates the system equivalent (or driving point) impedance as a function of frequency when shunt capacitors are applied. Note the shift of the parallel resonances, the points of high impedance, which occurs by varying the size of the capacitor bank. If these parallel resonances correspond to harmonic frequencies of nonlinear loads at the facility, they will cause significant voltage distortion. At industrial plants, almost all harmonic distortion occurs at the 5th and 7th, (and to a lesser extent 11th or 13th) harmonics, which are typical of adjustable speed drives (ASDs). In office buildings, distortion at the 3rd harmonic is possible due the electronic loads, such as computers.

Solutions to Harmonic Concerns

To reduce the above harmonic concerns, system operating restrictions may be applied, or the power factor correction capacitors can be configured as filters. The filters are tuned slightly below the harmonic frequency of concern to allow for the manufacturing tolerances in the filter components and system changes, and avoid stressing filter components.

General Guidelines for Filter Applications

1. Start with a single filter, tuned slightly below the lowest harmonic frequency e.g.: 4.7th harmonic (282 Hz) filter to avoid resonances at the 5th (300 Hz). The filter kVAR (size of the capacitor) should be established by the amount of power factor correction needed.

2. Check the driving point impedance of the system with the filter in place allowing for tolerances in filter components.

3. Check the distortion levels.

4. If the distortion levels are still high, provide additional filters for other harmonic frequencies. IEEE Std 519-1992 calls for a 5% limit on the voltage distortion for low voltage systems.

Transient overvoltages are always of concern when capacitors are switched. The concerns are twofold:

1. Overvoltages at the customer owned power factor capacitors (and therefore the customer's system) occurring when utility capacitors are switched.

2. Overvoltages within customer facilities associated with the switching of their power capacitors.

The analysis for the two above conditions is similar, and is presented in the following.

Overvoltages at The Switched Capacitors

When a capacitor is switched, a transient overvoltage oscillation occurs between the capacitor and the system inductance. This overvoltage can be as high as 2 per-unit (twice the normal voltage), but will normally be less due to damping in the system. If the capacitor switching device prestrikes (on closing) or restrikes (on opening), voltage across the capacitor can be doubled or tripled, depending on the number of prestrikes or restrikes.

Overvoltages at Locations Away From the Switched Capacitor (Voltage Magnification)

Switching of capacitor banks can create overvoltages at remote locations with smaller shunt capacitors. Figure 2 illustrates how the magnitude of the overvoltages is a function of both capacitor bank sizes. If larger capacitor is 10 times or more the smaller unit, the two circuits have similar resonant frequencies, and there is little damping in the system, the magnified transients can be in the range of 3.0 to 5.0 per unit. Such overvoltages can cause nuisance tripping of sensitive electronic equipment and stress system insulation causing damage to components such as motors and transformers.



Methods to Reduce Transient Overvoltages Due to Capacitor Switching

1. Use of switching devices that do not prestrike or restrike.

2. Synchronous switching of capacitors.

3. Installation of high energy metal oxide arresters.

4. Use of, properly designed, tuned filters in lieu of capacitors.

5. Use of isolation transformers or series reactors at the sensitive loads.

SELF EXCITATION OF INDUCTION MOTORS

When an induction motor and its power factor correction capacitor have a common switching device, transient overvoltages may upon opening that switching device. The capacitor bank, if improperly sized, will lead to the self-excitation of the motor, which will then act as a generator, resulting in some high overvoltages which may damage the motor and the capacitor.

To avoid potentially dangerous overvoltages at induction motor terminals, the kVAR rating of the motor-switchable power factor capacitor should not exceed the kVAr requirement to correct the no load power factor to unity.

HIGH INRUSH CURRENTS UPON BACK-TO-BACK SWITCHING OF CAPACITOR BANKS

Energizing a capacitor bank with another bank in service on the same bus may lead to high inrush currents which may damage the capacitors, cause the CTs to saturate, and blow capacitor fuses. The switching devices should also be rated for capacitor switching.

The voltage transients associated with back-to-back switching of capacitor banks are not considered to be problematic.

Proper application of multi-stage capacitor banks may require inrush-current-limiting reactors, or high induction type buses.

MEASURES TO REDUCE OVERVOLTAGES FROM CAPACITOR SWITCHING

Based on field experience, the following recommendations can be made regarding the application of shunt capacitors:

To avoid dynamic overvoltages, do not energize capacitor banks and transformers simultaneously.

To limit switching overvoltages and interference with sensitive components, do not energize capacitor banks within five minutes after their deenergization.

To eliminate ferroresonance, avoid situations which may lead to single-phasing a capacitor bank ( one leg of a Y or due to a fuse-blowing) connected to a transformer.

This paper is not a complete analysis or applicable to all systems. The application of capacitors for power factor correction and voltage support must be carefully considered to prevent operating difficulties and equipment damage. Each system is unique and solutions should be modeled on a computer to determine the optimum type of capacitor system, amounts of correction needed and where it should be installed.

Source: Nicholas Abi-Samra
Fellow Engineer
Westinghouse Electric Corporation
(714) 372-5640

Back to Home Page Back to Power Engineering Notes Page
1