Hygeia ProScience Laboratories, Inc.
On 2/5/96 at least one liter of water was drawn after a 12 hour wait from each the following apartment taps. On 2/7/96 the water was delivered to the testing laboratory. On 2/21/96 the results were returned to the tenant association. Please note that the Federal Safe Drinking Water Act "requires action be taken if lead levels at the tap exceed 15 parts per billion (or 0.015 milligrams of lead per liter.)"
LAB ID: Description/Location Result
L9963 W203 0.024 mg/L
L9964W310 0.016 mg/L
L9965 E401 0.012 mg/L
L9966 W121 0.020 mg/L
L9967 E417 0.025 mg/L
L9968 E518 0.015 mg/L
L9969E309 0.053 mg/L
L9970 W519 <0.005 mg/L
L9971 E113 0.010 mg/L
L9972 E207 0.023 mg/L
L9973 E104 <0.005 mg/L